Fieldbus Power Supply Series 9412

Fieldbus Power Supply Series 9412

  • For FOUNDATION fieldbusTM H1 acc. to IEC 61158-2
  • High power output up to 350 mA
  • Installation in Zone 2, Division 2 or in the safe area
  • Isolation between fieldbus segment and the input power supplies
  • Error message for power or bus failure via relay contact
  • LED indicators for simple diagnostics
  • Integrated fieldbus terminator

 

Type 9412/PS-I, 9412/PS-2

  • Redundant power and fieldbus supply for high availibility applications
  • Simple module replacement without fieldbus reset

 

Type 9412/PS-DT, 9412/PS-D

  • Redundant power connection
  • Dual channel fieldbus
Introduction Ordering codes Technical data Dimension drawings Documentation

The Fieldbus Power Supplies 9412/PS-I and 9412/PS-2 are used for the redundant supply and signal conditioning of none intrinsically safe FF H1 fieldbusses. The system consists of a carrier with two supply modules that can be exchanged in operation.

The Fieldbus Power Supplies 9412/PS-D and 9412/PS-DT are used for the supply and signal conditioning of up to two none intrinsically safe FF H1 fieldbusses. The system consists of a carrier with two supply modules.

The versions 9412/PS-I and 9412/PS-DT already includes the terminator for the fieldbus segment.

The fieldbus circuit and the supply for the Fieldbus Power Supply are monitored. If the voltage drops the required level an error message via a relay contact (normally closed) follows.

The units can be installed also in Zone 2 and Div. 2. For easy installation up to 8 Fieldbus Power Supplies (9412/PS-I and 9412/PS-2) or up to 5 dual Fieldbus Power Supplies (9412/PS-D and 9412/PS-DT) can be cascaded. All terminals are exchangeable.

Zone 2
KAT-AT

Selection Table

Version

Description

Ordering Code

Weight

kg
Fieldbus Power Supply Series 9412, redundant, with termination resistance

includes

2 fieldbus power supply modules type 9412/PS-IPM

1 module carrier type 9419/PS-RCT

+ terminals

9412/PS-I 0,573
Fieldbus Power Supply Series 9412, redundant, without termination resistance

includes

2 fieldbus power supply modules type 9412/PS-IPM

1 module carrier type 9419/PS-RC

+ terminals

9412/PS-2 0,573
Fieldbus Power Supply Series 9412, dual, with termination resistance

includes

2 fieldbus power supply modules type 9412/PS-IPM

1 module carrier type 9419/PS-DCT

+ terminals

9412/PS-DT 0,573
Fieldbus Power Supply Series 9412, dual, without termination resistance

includes

2 fieldbus power supply modules type 9412/PS-IPM

1 module carrier type 9419/PS-DC

+ terminals

9412/PS-D 0,573
KAT-TD

Technical Data

Explosion protection

Europa (ATEX): II 3 G EEx nA IIC T4

USA (FM): Class 1, Div. 2 Grps A-D
(in preparation)

Kanada (CSA): Class 1, Div. 2, Grps A-D; nA IIC T4 (in preparation)

Europa (ATEX): II 3 G EEx nA IIC T4

USA (FM): Class 1, Div. 2 Grps A-D
(in preparation)

Kanada (CSA): Class 1, Div. 2, Grps A-D; nA IIC T4 (in preparation)

Installation

safe area, Zone 2 or Div. 2
(Div. 2 in preparation)

safe area, Zone 2 or Div. 2
(Div. 2 in preparation)

Version

9412/PS-.

9412/PS-D.

Power supply

Rated voltage UN

24 V DC 24 V DC

Voltage range

19.2 V ... 30 V 19.2 V ... 30 V

Current consumption

at 350 mA output load

820 mA (typical); 895 mA (max.): at 18 V

630 mA (typical); 685 mA (max.): at 24 V

540 mA (typical); 600 mA (max.): at 28 V

with 2 x 350 mA output load

1.37 A (typical): at 20 V

1.14 A (typical): at 24 V

0.98 A (typical): at 28 V

Power dissipation

5.7 W (typical); with 350 mA output load

10.2 W; with 2 x 350 mA output load

Redundant power supply

yes yes

Max. number of cascaded units

8 5

Operating indication

LED per supply circuit, green

LED per module, green

LED per supply circuit, green

LED per module, green

Galvanic transmission

Fieldbus to power supply

250 V AC rms 250 V AC rms

Fieldbus

Spezification

IEC 61158-2 Foundation Fieldbus

IEC 61158-2 Foundation Fieldbus

Termination

integrated (9412/PS-I)

integrated (9412/PS-DT) for each channel

Output

Number of channels

1

2

Supply voltage

≥ 25.0 V

≥ 25.0 V

Supply current

0 mA ... 350 mA

0 mA ... 350 mA

Output ripple

complies with clause 22.6.2 of the fieldbus standard

complies with clause 22.6.2 of the fieldbus standard

Minimum load

no load no load

Error detection

Error in supply

< 18 V

< 18 V

Error in output circuit

< 22 V

< 22 V

Error messaging

Relay contact, normally closed; 1.0 A at 30 V DC

Relay contact, normally closed; 1.0 A at 30 V DC

Fault displays

error in output circuit; LED, green error in output circuit; LED, green

Electromagnetic compatibility

to EN 61326: 1998 to EN 61326: 1998

Ambient temperature

Ambient temperature

- 40 °C ... + 60 °C (horizontal DIN rail)

- 40 °C ... + 60 °C (horizontal DIN rail)

Storage temperature

- 40 °C ... + 85 °C

- 40 °C ... + 85 °C

Connection diagram

11086E02

11086E02

11085E02

11085E02

Mechanical data

Terminals

screw terminals

screw terminals

Installation

DIN-rail NS 35 acc. to EN 50022 DIN-rail NS 35 acc. to EN 50022

Mounting position

any any

Degree of protection

IP 20 IP 20

Enclosure material

fieldbus power supply module:

module carrier:

black, anodised aluminium

lexan polycarbonate

fieldbus power supply module:

module carrier:

black, anodised aluminium

lexan polycarbonate

Dimension drawings (all dimensions in mm) - subject to alterations

11083E00

11083E00

11084E00

11084E00

9412/PS-I, 9412/PS-2
Redundant Fieldbus Power Supply

9412/PS-DT, 9412/PS-D
Dual Fieldbus Power Supply

Certificates
Certification Body Country Type Certificate-Number Acceptance Category Language
Fieldbus Foundation United States 9412/.. PS002100 USA English [download]